System Specifications

Logic Control System

  • Control System shall use a minimum of 14 gauge direct burial wire with a maximum length of 12,000 feet per run.
  • Controller shall be mounted 15 feet from all electrical equipment and pumps.
    Control System shall have Surge Protection Device installed every 300 to 500 feet with ground rod. (user supplied)
  • Control System shall allow for field two-wire path to have unlimited Tees, Crosses and “Wagon Wheel” design.

Controller

  • Controller shall have No Power on field wires except when running a program.
    Controller shall apply power to field wires 15 seconds before a program(s) is scheduled to operate.

  • Controller shall have Lockout Security Code option for changing programming.

  • Controller shall have “bounce back technology” in case of power outage. Controller will resume program in “Real Time” when power resumes.

  • Controller will retain memory for 30 days in case of lost power without batteries.

  • Controller shall be able to set Date and Time of Day.

  • Controller shall have 42 stations (LogicPLUS 42) or 128 stations (Logic PLUS 128).

  • Controller shall have 8 programs and 8 Start Times per program (LogicPLUS 42) or 16 programs and 16 Start Times per program (LogicPLUS 128).

  • Controller shall have 6 programs with station Run Times from 1minute to 10 hours and 59 minutes in one minute increments and 2 programs with station Run Times from 1 second to 59 minutes 59 seconds in second increments (LogicPLUS 42) or 14 programs with station Run Times from 1 min to 10 hours and 59 minutes in one minute increments and 2 programs with station Run Times from 1 second to 59 minutes 59 seconds in second increments (LogicPLUS 128).

  • Controller shall have Fertigation capability per independent station.

  • Controller shall have PreWet Fertigation per independent station.

  • Controller shall be able to set PreWet time function and Fertigation time function per station in hours and minutes for all programs except two, which will be minutes and seconds.

  • Controller shall have a Pause option between stations
    sequencing in a program and Master Valve/ Pump On/Off
    option during Pause option.

  • Controller shall be able to show total Run Times per program, automatically adjusted if budget is adjusted.

  • Controller shall have a minimum of a one day calendar and a maximum of a 28 day calendar.

  • Controller shall be able to operate Odd or Even calendar days.
    Controller shall operate 7 day calendar by names of days of
    the week.

  • Controller shall have the ability to set watering days by calendar day.

  • Controller shall have a looping feature from one minute to 23 hours and 59 minutes. Looping feature shall be able to be activated by a remote sensor.

  • Controller shall be able to turn off individual programs.

  • Controller shall be able to control Master Valve/Pump Start by individual program.
    Controller shall be able to Water Budget from 5% to 250% in
    5% increments.

  • Controller shall have a test cycle to run each station from
    3 seconds to 10 minutes and 59 seconds sequentially.

  • Controller shall be able to clear individual programs or all
    programs automatically.

  • Controller shall be able to run a program manually. (semi-auto mode)

  • Controller shall be able to operate up to 4 stations manually. (manual mode)

  • Controller shall be able to have up to 31 days of Rain Delay function.

  • Controller shall be able to be turned On or Off without loosing Current Date or Time.

  • Controller shall display Auto (On) or Off, day of the week, current time and Days of Rain Delay

  • Controller shall display program # operating, valve # operating and valve time remaining.

  • Controller shall be able to program LogicPLUS Receivers from
    the controller.

  • Controller shall operate up to four valves simultaneously of the same or different numbers.

  • Controller shall be Radio Remote ready.

  • Controller shall be able to “field test for shorts”.

  • Controller shall have LED lights to confirm Master On and/or Fertigation On.

  • Controller shall provide four independent two-wire field outputs.
    Controller shall have Surge Protection modular removable
    circuit board.

  • Controller shall be able to operate at 120 VAC 60 Hz or
    230 VAC 50 Hz.

  • Controller shall be equipped with a 24 VAC transformer.

  • Controller shall be able to operate with a Normally closed
    Rain Sensor.

  • Controller shall be able to operate a Master Valve or Pump Start Relay up to 350 Ma.

  • Controller shall be able to operate a Fertigation relay up to 350 Ma.

  • Controller shall have a “Diamond” software function to control Calendar, Run times, Water Budget and Start Times from overlapping.

  • Controller shall be housed in a Stainless Steel cabinet with key lock, suitable for wall mount or optional pedestal mount.

Receiver

  • Receiver shall have two red wires to connect to the Control System two-wire path and two black wires to connect to any standard 24 VAC solenoid. (no diode bridge solenoids or special solenoids)
  • Receiver shall have LED light to confirm power on to receiver.

  • Receiver shall be gray in color.

  • Receiver shall be able to be fitted with Identification Tags on wire.

  • Receiver shall be shipped with two approved wire
    DBC-BR connectors.

  • Receivers shall be shipped 16 per carton with Identification Tags #1 through #128 included.

LogicPLUS Hand-Held Programmer

  • LogicPLUS Hand-Held Programmer shall be able to program receivers independent of the controller.

  • LogicPLUS Hand-Held Programmer shall be powered by 110 VAC plug in transformer or one 9V DC battery.

  • LogicPLUS Hand-Held Programmer shall have two blue wire leads for programming

  • LogicPLUS Receivers.

  • LogicPLUS Hand-Held Programmer shall be able to program receivers from #1 through #128.

  • LogicPLUS Hand-Held Programmer shall be able to test receivers from #1 through #128.

Part Numbers

  • LP-42 LogicPLUS 42 Station Controller

  • LP-128 LogicPLUS 128 Station Controller

  • L-PED Optional Stainless Steel Pedestal

  • LP-RP LogicPLUS Receiver

  • LP-HHRP LogicPLUS Hand-Held Programmer

  • L-RP-ID LogicPLUS Receiver Identification Tag set #1 through #128

  • LP-SPD-F LogicPLUS Surge Protection Line Device

  • DBC-BR LogicPLUS approved splice Kit (2-Splice Kits)

  • LP-RAD-SK Sidekick Radio Remote Controller Unit

CONTROL SYSTEM SPECIFICATIONS

Universal 2 PLUS Control System

  • Universal 2 System shall use a minimum of 14 gauge direct burial wire with a maximum length of 12,000 feet per run.

  • Universal 2 shall be mounted 15 feet from all high voltage electrical equipment and pumps.

  • Universal 2 Control System shall have Surge Protection Device installed every 300 to 500 feet with ground rod. (user supplied)

  • Universal 2 Control System shall allow for field two-wire path to have unlimited Tees, Crosses and “Wagon Wheel” design.

  • Converter

  • Converter shall have No Power on field wires except when running a program.

  • Converter shall have 40 stations.

  • Converter shall operate up to 4 valves simultaneously of the same or different numbers.

  • Converter shall provide two independent two-wire field outputs.

  • Converter shall be able to operate at 120 VAC 60 Hz or 230 VAC 50 Hz.

  • Converter shall be equipped with a 24 VAC transformer.

  • Converter shall be able to operate a Master Valve or Pump Start Relay up to 350 Ma.
    Converter shall be housed in a Stainless Steel cabinet with key lock, suitable for wall mount or optional pedestal mount.

  • Converter shall be compatible with all standalone and satellite controllers with standard 24 VAC output.

  • Converter shall utilize LogicPLUS two-wire technology to turn standard 24 VAC solenoid valves on and off as per the controller.

  • Converter shall utilize a two-wire path and a receiver at each valve to operate up to 40 different numbered valves.

  • Converter shall utilize infrared switching technology to isolate Converter and Controller from any feed back.

  • Converter shall provide a resettable overload switch to protect against damage due to shorts in field wiring or valve solenoids.

  • Converter shall require an 18 gauge wire to be connected from each Controller terminal to each same numbered terminal connection on the Universal Plus 2 converter.

Receiver

  • Receiver shall have two Red wires to connect to Control System two-wire path and two black wires to connect to any standard 24 VAC solenoid. (no diode bridge solenoids or special solenoids).

  • Receiver shall have LED light to confirm power on to receiver.

  • Receiver shall be Gray in color.

  • Receiver shall be able to be fitted with number identification tags on wire.

  • Receiver shall be shipped with two approved DBC-BR wire connectors.

  • Receivers shall be shipped 16 per carton with Identification Tags #1 through #40.

LogicPLUS Hand-Held Programmer

  • LogicPLUS Hand-Held Programmer shall be able to program receivers to desired valve number.

  • LogicPLUS Hand-Held Programmer shall be powered by 110 VAC plug in transformer or one 9V DC battery.

  • LogicPLUS Hand-Held Programmer shall have two blue wire leads for programming LogicPLUS Receivers.

  • LogicPLUS Hand-Held Programmer shall be able to program receivers from #1 through #40.
    LogicPLUS Hand-Held Programmer shall be able to test receivers from #1 through #40.

 

 